K2 Series 6.0
- Discrete 254nm TeflonTM based UV sensor (user selectable output) with 4-20 mA output and solenoid-ready
- Modular 304 stainless steel control panel with LED display for UV output, remaining lamp life, total running hours, audible & visual lamp failure, remote-on and dry contacts
- 316L stainless steel, polished reactors with flanged end-plate
- Designed & manufactured to ASME pressure vessel standards
- Flow rates stated at 95% UVT at a dose of 30 mJ/cm2
- User friendly bayonet style lamp connectors (quick ¼ turn removal with no extra tools needed)
- True gland seal retaining nuts with positive stop
- Reliable, industry proven low pressure amalgam (LP-AM) coated UV lamps with ceramic bases for durability and a 12,000 hour lamp life
- Constant current electronic ballasts
Commercial / Industrial Disinfection Solutions
LUMINOR’s K2 line of disinfection systems are specifically designed and built to handle the challenging environments of process and manufacturing industries as well as pool and leisure applications.
K26.0 includes a discrete 254nm TeflonTM based UV sensor to continuously monitor the UV output produced by the system. Displayed on the LCD screen in either “% UV Intensity” or “mW/cm2 “, K26.0 provides the information that these demanding commercial /industrial systems require. Constructed with highly polished 316L stainless steel reactors and stainless steel enclosures, K26.0 uses proven low pressure amalgam (LP-AM) lamp technology for maximum power density and efficiency all in a small footprint.
Controlling microbiological (bacteria & virus) issues in water (or other viscous fluids), including E.coli, Cryptosporidium, and Giardia lamblia is safe and simple with LUMINOR UV systems. UV does not affect the aesthetic quality of the fluid and the process does not add anything to the fluid, nor create any disinfection by-products.
Covering a wide variety of applications in both regulated and unregulated markets, K2 offers environmentally friendly disinfection at lower capital and operating costs than traditional disinfection solutions.
Whether you are looking to control microbiological issues in both hot or cold water with UVT levels as low as 50% or to reduce TOC in industrial grade waters, K26.0 has you covered.
Applications Include:
- Food & Beverage
- Pharmaceutical
- Swimming Pools
- Water Reuse
- Ultrapure
- Recreational Water
- Aquaculture
- Municipal
Available Systems
- LK6-A12 for flow rates of 322 lpm (85 gpm) (20 m3/hr)
- LK6-A22 for flow rates of 662 lpm (175 gpm) (40 m3/hr)
- LK6-A42 for flow rates of 1500 lpm (400 gpm) (91 m3/hr)
- LK6-A62 for flow rates of 2400 lpm (625 gpm) (142 m3/hr)
K26.0, Commercial / Industrial / Municipal UV Systems, UV Monitored | ||||
Model | LK6-A12 | LK6-A22 | LK6-A42 | LK6-A62 |
Flow Rate (@16mJ/cm2)* |
167 GPM | 327 GPM | 758 GPM | 1170 GPM |
632 lpm | 1240 lpm | 2870 lpm | 4429 lpm | |
37.9 m3/hr | 74.3 m3/hr | 87.7 m3/hr | 265.8 m3/hr | |
Flow Rate (@30mJ/cm2) |
85 GPM | 175 GPM | 400 GPM | 625 GPM |
322 lpm | 662 lpm | 1500 lpm | 2400 lpm | |
20 m3/hr | 39.7 m3/hr | 91 m3/hr | 142 m3/hr | |
Flow Rate (@40mJ/cm2) |
67 GPM | 131 GPM | 303 GPM | 467 GPM |
252 lpm | 496 lpm | 1150 lpm | 1768 lpm | |
15.1 m3/hr | 29.8 m3/hr | 68.8 m3/hr | 106.1 m3/hr | |
Port Size | 2" MNPT | 3” Flange | 4" Flange | 6" Flange |
Electrical | 220V/50-60Hz | |||
Electrical Connection | Direct Wire | |||
Lamp Watts | 207 | 414 | 828 | 1242 |
Power (Watts) | 240 | 460 | 900 | 1340 |
Chamber Material | 316L Stainless Steel, A249 Pressure Rated Tubing, Polished & Passivated | |||
Replacement Lamp | RL-1000A (1 required) |
RL-1000A (2 required) |
RL-1000A (4 required) |
RL-1000A (6 required) |
Replacement Sleeve | RQ-K2 (1 required) |
RQ-K2 (2 required) |
RQ-K2 (4 required) |
RQ-K2 (6 required) |
Reactor Dimensions | Contact Factory | |||
Controller Dimensions | Contact Factory | |||
Maximum Operating Pressure |
10.3 bar (150 psi) | |||
Operating Temperature Range |
2-60° C (36-148° F) | |||
254nm UV Intesity Monitor | Yes | |||
UVT Monitoring | Optional / Upgradeable | |||
Dose Calculations | Optional / Upgradeable | |||
Flow Monitoring | Optional / Upgradeable | |||
Internal Fault History | Yes | |||
Remote - On | Yes | |||
Dry Contacts (Solenoid Ready) |
Yes | |||
4-20 mA Output | Yes | |||
Drain Ports | Yes, 3/8” | Yes, ½” | ||
Lamp Age Counter | Yes | |||
Sample Ports | No | Yes | ||
Visual Lamp-Out Indicator | Yes | |||
Audible Lamp-Out Alarm | Yes | |||
Shipping Weight | Contact Factory |